Redland Addition
Septic System
Architectural Plans
Building Codes
Insulation
Electrical
Panel & Circuit Plan
Circuits
AFCI + GFCI
(20a) Bedroom 1 receptacles
(20a) Bedroom 2 + Basement Hall + Basement Hall Closet receptacles
(20a) Master Bedroom + Master Closet + Master Hall receptacles
(20a) Lighting for BR 1/BR 2/Master BR/Basement closet/Basement hall/Master hall/Master closet
(20a) Master bathroom receptacles
(20a) Master bathroom lighting/exhaust/heat lamp
(20a) Master closet washing machine receptacle
(20a) Master tub circulation receptacle
(20a) Master tub heater receptacle
Standard
(30a 240 volt) Heat pump circuit
To purchase
-
Panel options
Subpanel wire
Siemens breaker
Outlets
Receptacle counts
Actual expected usage
Amperage across all new circuits if all expected loads were turned on at once.
| Circuit | Expected usage (amps) |
| Bedroom 1 receptacles | 3.5 |
| Bedroom 2 + Basement Hall + Basement Hall Closet receptacles | 3.5 |
| Master Bedroom + Master Closet + Master Hall receptacles | 3.5 |
| Lighting for BR 1/BR 2/Master BR/Basement closet/Basement hall/Master hall/Master closet | 1.5 |
| Master bathroom receptacles | 12.5 |
| Master bathroom lighting/exhaust | 3 |
| Master closet washing machine receptacle | 11 |
| Master tub circulation receptacle | 9 |
| Master tub heater receptacle | 12.5 |
| Heat pump circuit | 23 |
| Total | |
2023 Codes
Required number of branch circuits
-
-
-
In addition to the number of branch circuits required by other parts of this section, one or more 120-volt, 20-ampere branch circuit shall be provided to supply bathroom(s) receptacle outlet(s) required by 210.52(D) and any countertop and similar work surface receptacle outlets. Such circuits shall have no other outlets.
Exception: Where the 20-ampere circuit supplies a single bathroom, outlets for other equipment within the same bathroom shall be permitted to be supplied in accordance with 210.23(B)(1) and (B)(2).
AFCI
Circuit conductor sizing
Circuit conductor sizing
Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125 percent of the continuous load.
The minimum branch-circuit conductor size shall have an ampacity not less than the maximum load to be served after the application of any adjustment or correction factors in accordance with 310.15.
-
Permissible loads
15 and 20 amp circuits
A 15- or 20-ampere branch circuit shall be permitted to supply lighting outlets, lighting units, or other utilization equipment, or any combination of them, and shall comply with 210.23(B)(1) and (B)(2).
Exception: The small-appliance branch circuits, laundry branch circuits, and bathroom branch circuits required in a dwelling unit(s) by 210.11(C)(1), (C)(2), and (C)(3) shall supply only the receptacle outlets specified in that section.
Branch circuit requirements summary
Receptacle Outlets
Spacing – no more than 6 feet between outlets
Bathrooms
Unless prohibited in 406.9(C), at least one receptacle outlet shall be installed in bathrooms within 900 mm (3 ft) of the outside edge of each sink. The receptacle outlet shall be located on a wall or partition that is adjacent to the sink or sink countertop, located on the countertop, or installed on the side or face of the sink cabinet. In no case shall the receptacle be located more than 300 mm (12 in.) below the top of the sink or sink countertop. Receptacle outlet assemblies listed for use in countertops shall be permitted to be installed in the countertop.
-